ETC Installation Guide
Unison
®
Echo Occupancy/Vacancy Sensor
Corporate Headquarters
3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA
Tel +608 831 4116
Fax +608 836 1736
London, UK
Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK
Tel +44 (0)20 8896 1000
Fax +44 (0)20 8896 2000
Rome, IT
Via Pieve Torina, 48, 00156 Rome, Italy
Tel +39 (06) 32 111 683
Fax +44 (0)20 8752 8486
Holzkirchen, DE
Ohmstrasse 3, 83607 Holzkirchen, Germany
Tel +49 (80 24) 47 00-0
Fax +49 (80 24) 47 00-3 00
Hong Kong
Rm 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong
Tel +852 2799 1220
Service:
(Americas) service@etcconnect.com
(UK) service@etceurope.com
(DE) techserv-hoki@etcconnect.com
Web:
www.etcconnect.com
Copyright © 2014 ETC. All Rights Reserved.
Product information and specifications subject to change.
7186M2180
Rev A
Released 2014-07
ETC intends this document to be provided in its entirety.
Overview
The Echo Occupancy/Vacancy Sensor is a ceiling mounted sensor that utilizes
passive infrared (PIR) technology, providing reliable vacancy and occupancy
detection for lighting control. The sensor provides automatic configuration of
vacancy (auto-off) or occupancy (auto-on/off) functionality based on other
connected control stations. When manual control stations are present, the
sensor will only perform vacancy actions.
Each sensor is available in white or black finish. Lens masks are provided to
allow customized occupancy detection fields as required by each installation.
Wire Specification
Sensors connect to the EchoConnect communication bus. EchoConnect is a
bidirectional protocol that uses one pair of wires (data + and data -) for both
data and power. ETC recommends using Belden 8471 (or approved equal)
Class II wire. The total combined length of an EchoConnect wire run (using
Belden 8471, or equal) may not exceed 1,640 feet (500m).
Note:
All control wiring should be installed and terminated by a qualified
installer and should follow standard wiring installation practices.
Leave approximately 10 inches (254mm) of wiring in the back box
for connection to allow slack for future service needs.
Note:
ETC requires that all sensors be grounded. Pull an additional 14
AWG (1.5mm
2
) wire for grounding when control wires are not
installed in grounded metal conduit.
The Occupancy/Vacancy Sensor provides 360
degree coverage of the installed location and is
available in three models:
E-OCC-SR- Occupancy/Vacancy Sensor with
small room lens covers 450 sq. ft. at 8 ft./
800 sq. ft. at 10 ft.
E-OCC - Occupancy/Vacancy Sensor with
standard room lens covers 1,800 sq. ft. at 8 ft./
3,000 sq. ft. at 10 ft.
E-OCC-HC - Occupancy/Vacancy Sensor with
high ceiling lens covers 300 sq. ft. at 10 ft./
7,000 sq. ft. at 40 ft.
Seitenansicht 0
1 2 3 4 5 6 7 8 9 10

Inhaltsverzeichnis

Seite 1 - ETC Installation Guide

ETC Installation GuideUnison® Echo Occupancy/Vacancy SensorCorporate Headquarters  3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 535

Seite 2

ETC Installation GuideOccupancy/Vacancy SensorOccupancy/Vacancy Sensor Install Guide Page 10 of 10High Ceiling side view03.0m10ft3.0m10ft6.1m20ft6.1m

Seite 3

ETC Installation GuideOccupancy/Vacancy SensorOccupancy/Vacancy Sensor Install Guide Page 2 of 10Installation EnvironmentOccupancy/Vacancy Sensors are

Seite 4

ETC Installation GuideOccupancy/Vacancy Sensor Page 3 of 10 Occupancy/Vacancy Sensor Install GuideInstallationThe Occupancy/Vacancy Sensor is provided

Seite 5

ETC Installation GuideOccupancy/Vacancy SensorOccupancy/Vacancy Sensor Install Guide Page 4 of 10Step 5: Strip each wire 5/16” (8mm) and terminate the

Seite 6

ETC Installation GuideOccupancy/Vacancy Sensor Page 5 of 10 Occupancy/Vacancy Sensor Install GuideStep 3: Create a hole for wire pass-through in the c

Seite 7

ETC Installation GuideOccupancy/Vacancy SensorOccupancy/Vacancy Sensor Install Guide Page 6 of 10Set Station ConfigurationOccupancy/Vacancy Sensors ha

Seite 8

ETC Installation GuideOccupancy/Vacancy Sensor Page 7 of 10 Occupancy/Vacancy Sensor Install GuidePower Up and TestPower UpAll EchoConnect termination

Seite 9

ETC Installation GuideOccupancy/Vacancy SensorOccupancy/Vacancy Sensor Install Guide Page 8 of 10Vacancy TimeoutVacancy timeout is the amount of time

Seite 10

ETC Installation GuideOccupancy/Vacancy Sensor Page 9 of 10 Occupancy/Vacancy Sensor Install GuideTestOccupancy/Vacancy Sensors offer a Walk Test mode