6 Unison® ERn Wall Mount Enclosure Installation ManualPreparationsUnpack and InspectBefore you begin installation, check your shipment and confirm it
1 Prepare for Installation 7General Lockout/Tagout Procedures:• Notify all affected employees that a lockout/tagout procedure is ready to begin.• Turn
8 Unison® ERn Wall Mount Enclosure Installation ManualWhere to Install the EnclosureThe Unison External Processing Enclosure (ERn) can be wall (surfac
1 Prepare for Installation 9Wire RequirementsWire Routing and SpecificationUnison ERn enclosures have conduit knockouts on the top and bottom for inco
10 Unison® ERn Wall Mount Enclosure Installation ManualThe following table lists the recommended control wire types used in a typical Unison installat
2 Install Rack Enclosures 11Chapter 2Install Rack EnclosuresThis chapter contains instructions for installation of the ERn enclosure and rough-in of c
12 Unison® ERn Wall Mount Enclosure Installation ManualInstall the Rack EnclosureThe wall must be strong enough to hold the rack fully populated with
2 Install Rack Enclosures 13Rough-in Conduit and WiringRemove Option ModulesPrior to installing conduit and pulling wires into the ERn enclosure, remo
14 Unison® ERn Wall Mount Enclosure Installation ManualRough-in Line and Control Conduit and WiringThe ERn enclosure requires line power and control w
3 Terminate Wiring 15Chapter 3Terminate WiringThis chapter contains the following sections:• Connect Line Power Wiring . . . . . . . . . . . . . . .
ETC®, Unison®, EDMX™ are either registered trademarks or trademarks of Electronic Theatre Controls, Inc. in the United States and other countries.Eche
16 Unison® ERn Wall Mount Enclosure Installation ManualConnect Line Power WiringERn enclosures are available in 100-120, 230 CE, and 240 VAC single ph
3 Terminate Wiring 17Connect Control WiringLow voltage data connects to pluggable connectors on the left and right input/output boards of the ERn encl
18 Unison® ERn Wall Mount Enclosure Installation ManualConnect ERn Right I/O Data TerminationsTerminate DMX Control WiringDMX wire preparation and ter
3 Terminate Wiring 19DMX Input/Output Termination: Insulation Displacement ConnectorsThe graphic below illustrates DMX termination layout for an insul
20 Unison® ERn Wall Mount Enclosure Installation ManualStep 2: Strip 3/16” (5mm) if insulation from the ends of each wire pair.Step 3: Remove the Link
3 Terminate Wiring 21DMX TerminationDMX requires 120 termination at the last DMX device in the control run. Since an ERn enclosure with a Paradigm Ar
22 Unison® ERn Wall Mount Enclosure Installation ManualConnect to Ethernet RJ-45Network interface to the ERn enclosure is made through the RJ-45 conne
4 Final Installation and Power Up 23Chapter 4Final Installation and Power UpThis chapter contains the following sections:• Check Main Power Wiring . .
24 Unison® ERn Wall Mount Enclosure Installation ManualCompleting the InstallationIt’s a good idea to look over the entire installation before applyin
4 Final Installation and Power Up 25Step 3: Open the ERn door and check voltage between phase, neutral, and ground. The ERn supports input power rangi
Table of Contents iTable of ContentsIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . . 1ERn External Processing Rack . . . . . . . . . .
26 Unison® ERn Wall Mount Enclosure Installation ManualChapter 5Install Rack OptionsThis chapter contains the following sections:• Install the RideThr
5 Install Rack Options 27Rack OptionsUnison ERn options include the RideThru Option (URTO) kit, BatteryPack Option kit (UBPO), Ethernet Switch Module
28 Unison® ERn Wall Mount Enclosure Installation ManualStep 1: Remove modules from the ERn enclosure for RideThru Option board installation access.• F
5 Install Rack Options 29Install the BatteryPack Option (UBPO) KitStep 1: The BatteryPack Option board is provided with a wiring harness for connectio
30 Unison® ERn Wall Mount Enclosure Installation ManualStep 2: Install the Unison BatteryPack on to the bottom of the ERn enclosure as pictured below.
5 Install Rack Options 31Install a Paradigm Repeater or Dual Repeater ModuleBoth repeater module types may only be utilized in the top module slots of
32 Unison® ERn Wall Mount Enclosure Installation ManualTerminate LinkConnect Control WiringUnison control stations communicate with the Paradigm Archi
5 Install Rack Options 33Step 4: Loosen the terminal screws for as many wire pairs you are terminating. Keep in mind that the connector is split into
34 Unison® ERn Wall Mount Enclosure Installation ManualStatus IndicatorsWhen power is applied to the ERn enclosure, the Paradigm Station Repeater Modu
5 Install Rack Options 35Install Redundant Power SupplyThe ERn Redundant Power Supply (ERn-RPS) is an additional rack power supply that powers the ERn
ii Unison® ERn Wall Mount Enclosure Installation ManualTerminate Contact Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . .22Final Installa
36 Unison® ERn Wall Mount Enclosure Installation ManualInstall the Ethernet Switch ModuleThe ERn Ethernet Switch Module installs in the bottom option
5 Install Rack Options 37Connect CAT5e WiringStep 1: Pull your CAT5e building wire through the conduit access previously prepared.Step 2: The punch do
38 Unison® ERn Wall Mount Enclosure Installation ManualStatus IndicatorsWhen power is applied to the ERn enclosure, the Paradigm Ethernet Switch Modul
5 Install Rack Options 39
Corporate Headquarters 3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA Tel +608 831 4116 Fax +608 836 1736London,
Introduction 1IntroductionWelcome to the installation manual for the Unison® ERn Enclosure. This manual contains the procedures for safe and efficient
2 Unison® ERn Wall Mount Enclosure Installation ManualERn Modules and OptionsModelPart NumberDescription NotesP-ACP 7180A1001 Paradigm Architectural C
Introduction 3ERn-NET 7180A1400 ERn Ethernet Switch ModuleThe ERn Ethernet Switch (ERn-NET) provides four ports of 802.3af compliant Power over Ethern
4 Unison® ERn Wall Mount Enclosure Installation ManualWarnings and Notice ConventionsThese symbols are used throughout this installation manual to ale
1 Prepare for Installation 5Chapter 1Prepare for InstallationThis chapter contains the following sections:• Preparations . . . . . . . . . . . . . . .