Matrix II Rack Installation Manual RA (Rear Access) and SF (Swing Frame) version racks Revision A Copyright
Matrix Mk.II Rack Installation Manual Local Requirements European Requirements Matrix II has been designed to European standards for electrical swit
Preparation for Installation 7 1 Dimmer Room Requirements Location o A clean (not dusty) temperature-controlled environment o Restricted public ac
Matrix Mk.II Rack Installation Manual Accessibility Allowing space around the rack (Rear access racks) o Rear access racks require adequate space i
Installation of Racks 9 2 Section 2 Positioning of Racks Description (Rear Access racks) Rear access racks are available in 160cm or 200cm high vers
Matrix Mk.II Rack Installation Manual Positioning Racks The racks are heavy, so it is advisable to prepare carefully before moving the racks into th
Installing Main Supply Cables 11 3 Section 3 Installing Main Supply Cables WARNING: Ensure that it remains impossible to apply power to the main su
Matrix Mk.II Rack Installation Manual Fuses The fuse protection employed in the rack provides a single 63A Siemens type D02 for each module position
Installing Data Cables 13 5 Section 4 Installing Load Cables Terminations Terminals for the load wiring are located to the left of the rack at the r
Matrix Mk.II Rack Installation Manual Section 5 Installing Data Cables All Matrix II dimmer racks accept data in Ethernet and discrete DMX formats.
Finishing Installation 15 6 Section 6 Finishing Installation Visual inspection After the supply, load and data terminations are completed, the rack
Matrix MkII Racks – standard range Rear Access Rack max capacity (160cm high) Rear Access Rack max capacity (200cm high) 7541A1714: 72 x 16A 7541A1
Matrix Mk.II Rack Installation Manual Section 7 Check Power Installation Checking main power wiring WARNING: Power must be turned OFF when you per
Installing Processor and Modules 17 8 Section 8 Installing the Processor and Modules CAUTION: Before unpacking and installing the electronic modul
Matrix Mk.II Rack Installation Manual Installing the modules WARNING: Do not force any module into a connector if resistance is felt. This could me
Preventative Maintenance 19 9 Section 9 Preventative Maintenance ETC Matrix II dimming systems are designed for long and reliable service, but will
Matrix Mk.II Rack Installation Manual Appendix A Troubleshooting Power loss Total power failure If all power to the rack fails (if it is not already
Troubleshooting 21 A To check module power and data WARNING: The Matrix rack has inherent safety from electrical shock if a module is removed with
Matrix Mk.II Rack Installation Manual Fan not working With Matrix II, the ventilation fans are located in each module. They are activated only when
Specifications 23 B Appendix B Matrix Mk.II Rack Specifications General Racks are available in nine configurations: 1.6m high Rear Access (RA) racks
Matrix Mk.II Rack Installation Manual Part numbers – main product items Racks 7541A1714 1.6m RA Rear Access Rack, 72ch 18 modules 4x16A 7541A1715 1.
Specifications 25 B Part numbers – factory configured option kits Note: Factory option kits below are available to change the output wiring. This m
Contents i Table of Contents Introduction ... 1 How to use this guide ...
Matrix Mk.II Rack Installation Manual Appendix C Conformity Certificates
Matrix Mk.II Rack Installation Manual Corporate Headquarters 3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA Tel
Matrix Mk.II Rack Installation Manual Section 7 Check Power Installation ... 16 Checking Main Power Wiring ...
Introduction 1 Introduction Welcome to the installation manual for Matrix® Mk.II dimmer racks. This manual contains the procedures for safe and eff
Matrix Mk.II Rack Installation Manual Module compatibility chart Rack version Rear access Swing frame Rack height 1.6m 2.0m 2.0m Channels (max)
Introduction 3 Rack version Rear access Swing frame Rack height 1.6m 2.0m 2.0m Channels (max) 72 108 72 54 108 162 108 81 108 162 108
Matrix Mk.II Rack Installation Manual Contacting ETC® For questions about Matrix Mk.II rack system delivery, contact ETC Systems Group. For general
Preparation for Installation 5 1 Section 1 Preparing for Installation Unpack and Inspect Before starting the installation, check the shipment to con